Tower Electric and Magnetic Fields Title
 

132 kV underground cables: magnetic field

see also:

Two main types of 132 kV underground cable are used.

  • separate cores: the three conductors for the three phases are laid separately but close together in the ground, typically 1 m deep
  • single cable: the three cores are twisted round each other in a single outer sheath. 

With a single cable, because the cores are so close together and twisted, the fields they produce directly are very small.  Instead, the field comes from any net current in the sheath.  This cannot be predicted accurately.

The following graph shows typical fields for these two types of cable (separate cores produce higher fields close to the cable but lower fields away from it).

Underground cables do not produce any external electric fields.

This table gives some actual field values for the same conditions.

       

magnetic field in µT at distance from centreline

0 m

5 m

10 m

20 m

132 kV

separate cores

0.3 m spacing

1 m depth

typical

9.62

1.31

0.36

0.09

single cable

1 m depth

typical

5.01

1.78

0.94

0.47

Notes

1. All fields calculated at 1 m above ground level

2. All fields are given to the same resolution for simplicity of presentation (0.01 µT = 10 nT) but are not accurate to better than a few percent.

3. Calculations for separate cores ignore zero-sequence current.  This means values at larger distances are probably underestimates, but this is unlikely to amount to more than a few percent.

4. Cable designs are not standardised to the same extent as overhead lines and the examples given here are representative.

5. In practice, there are often several cables nearby, and the fields interact with each other.