Tower Electric and Magnetic Fields Title
 

400 kV overhead lines: magnetic field

see also:

400 kV is the highest voltage in use in the UK.

The maximum field is produced by the largest design of line – the L6 – when the ground clearance is the minimum allowed – 7.6 m – and the loads are the highest allowed – 4.7 kA in each circuit.  The field also depends on the phasing. Transposed (T) is higher close to the line and Untransposed (U) is higher away from the line.  This graph shows both.

Typical fields are lower than the maximum field because the clearance is usually higher and the loads are usually lower.  Also, many lines are a slightly smaller design – the L2.  Both L6 and L2 are shown on the following graph.  The phasing here is T as this is more common. It is rare for the two circuits to carry exactly the same load.  That is why the magnetic field shown here is not symmetrical.

see also fields calculated from one year of actual load data

Larger 400 kV pylon (L6):  Smaller 400 kV pylon (L2):

This table gives some actual field values for the same conditions.

         

magnetic field in µT at distance from centreline

maximum under line

10 m

25 m

50 m

100 m

400 kV

largest lines

L6
quad bundles
0.305 m
zebra

maximum

clearance 7.6 m
phasing U
load 4.7/4.7 kA

108.422

95.780

38.422

11.697

3.096

typical

clearance 13 m
phasing T
load 0.4/0.6 kA

5.783

5.247

2.194

0.578

0.119

smaller lines

L2
twin bundles
0.305 m
zebra

maximum

clearance 7.6 m
phasing U
load 2.4/2.4 kA

54.142

46.300

16.283

4.865

1.278

typical

clearance 13 m
phasing T
load 0.4/0.6 kA

4.971

4.158

1.557

0.400

0.084

typical design used for new lines

L12
twin bundles
0.5 m
araucaria

maximum

clearance 7.6 m
phasing U
load 3.5/3.5 kA

81.942

72.818

22.103

8.148

2.145

typical

clearance 13 m
phasing T
load 0.4/0.6 kA

5.604

4.938

1.979

0.514

0.106

Note:

1. All fields calculated at 1 m above ground level.

2. All fields are given to the same resolution for simplicity of presentation (1 nT = 0.001 µT) but are not accurate to better than a few percent.

3. Calculations ignore zero-sequence current.  This means values at larger distances are probably underestimates, but this is unlikely to amount to more than a few percent and less closer to the line.

4. The “maximum field under the line” is the largest field, which is not necessarily on the route centreline; it is often under one of the conductor bundles.

5. Calculated fields agree well with measured fields.  more