Tower Electric and Magnetic Fields Title
 

Overhead Lines

Tables of calculated electric fields produced by overhead lines in operation in the UK

See also the companion table for magnetic fields, underground fields and the simpler summary

         

electric field in V m-1 at distance from centreline

maximum under line

10 m

25 m

50 m

100 m

400 kV

largest lines

L6
quad bundles
0.305 m
zebra

maximum

clearance 7.6 m
phasing U

11400

10130

774

446

156

typical

clearance 13 m
phasing T

4244

4206

962

106

32

smaller lines

L2
twin bundles
0.305 m
zebra

maximum

clearance 7.6 m
phasing U

9897

6618

283

357

118

typical

clearance 13 m
phasing T

3128

2964

469

56

27

typical design used for new lines

L12
twin bundles
0.5 m
araucaria

maximum

clearance 7.6 m
phasing U

10642

8410

669

404

136

clearance 7.6 m
phasing T

9384

7933

737

151

30

typical

clearance 13 m
phasing T

3704

3595

732

98

26

275 kV

largest lines

L6
quad bundles
0.305 m
zebra

maximum

clearance 7.6 m
phasing U

7838

6964

532

307

107

typical

clearance 13 m
phasing T

2918

2892

661

73

22

smaller lines

L2
twin bundles
0.305 m
zebra

maximum

clearance 7.6 m
phasing U

6804

4550

195

245

81

typical

clearance 13 m
phasing T

2151

2038

322

39

19

typical design used for new lines

L12
twin bundles
0.5 m
araucaria

maximum

clearance 7.6 m
phasing U

7316

5782

460

278

94

typical

clearance 13 m
phasing T

2547

2472

503

67

18

132 kV

largest lines

L7
twin bundles
0.305 m
lynx

maximum

clearance 7 m
phasing U

3615

913

182

81

23

typical

clearance 10 m
phasing U

2372

890

103

72

23

smaller lines

L132
single conductors
0.4 sq in

maximum

clearance 7 m
phasing U

2628

697

154

66

19

typical

clearance 10 m
phasing U

1780

689

86

59

18

smallest wood-pole design

trident
150 m span
single conductors
lynx

maximum

clearance 7 m
single circuit

1174

588

73

11

2

typical

clearance 10 m
single circuit

583

458

89

15

3

66 kV

largest lines

L7
twin bundles
0.305 m
lynx

maximum

clearance 7 m
phasing U

1808

456

91

40

12

smaller lines

L132
single conductors
0.4 sq in

typical

clearance 10 m
phasing U

890

345

43

30

9

33 kV

larger lines on steel pylons

D
single conductors
r=9.8 mm

maximum

clearance 5.5 m
phasing U

897

46

30

10

3

typical

clearance 8 m
phasing U

543

81

21

9

3

smaller lines on wood poles

wood pole
horizontal array
+-2 m

maximum

clearance 5.5 m
single circuit

505

165

16

2

0

typical

clearance 8 m
single circuit

241

147

21

3

0

11 kV

larger lines on steel pylons

SL11
single conductors

maximum

clearance 5.5 m
phasing U

215

109

13

5

1

typical

clearance 8 m
phasing U

122

82

8

4

1

smaller lines on wood poles

wood pole
horizontal array
+-1.15 m

maximum

clearance 5.5 m
single circuit

108

32

3

0

0

typical

clearance 8 m
single circuit

50

29

4

1

0

400 V

wood pole

vertical array
50 mm2

maximum

clearance 5.5 m
single circuit

1

1

0

0

0

typical

clearance 8 m
single circuit

0

0

0

0

0

 Notes to table:

1. Calculations performed on computer programme EM2D by John Swanson January 2005.

2. Typical phases are T=transposed for 275 kV and 400 kV, U=untransposed for 132 kV and below (phases apply to double-circuit lines only)

3. For electric fields, U always gives the highest maximum field and the highest field at large distances, so is used for that reason, but at intermediate distances from the line, electric fields are complex, and either T or U can be higher.

4. The “maximum field under the line” is the largest field, which is not necessarily on the route centreline; it is often under one of the conductor bundles for a two-circuit line and can even be outside the conductors eg for a 400 V vertical array.

5. All fields calculated at 1 m above ground level and for nominal voltage

6. All fields are given to the same resolution for simplicity of presentation (1 V/m) but are not accurate to better than a few percent.

7. Calculations ignore zero-sequence voltage.  This means values at larger distances are probably underestimates, but this is unlikely to amount to more than a few percent except for 400 V lines.

8. Generally speaking, the lower the voltage, the more different variants of design there are.  The “maximum” calculation is presented here in good faith but may not take account of every last variant in operation.  To meet specific local circumstances, lines at 132 kV and below may occasionally have been constructed with higher ratings.  Within the legal framework of the Regulations, different DNOs may have different policies regarding minimum clearances.

9. All calculations are for three-phase lines, single-phase lines at low voltages have not been investigated.

Notes on specific voltages:

1. In efforts to reduce aerodynamic problems, a small number of 400 kV lines with quad bundles have had expanded bundles fitted, eg 500 mm horizontally.  This produces slightly higher electric fields but is not included in these tables.

2. For 400 kV, L12 lines are included as these are likely to be used for new construction. Phasing U gives the maximum field under the line and is included for that reason but phasing T would be used in practice so is also included.

3. 132 kV lines have, in the past, been constructed on 275/400 kV towers with a view to future uprating.  This is unlikely to happen again so is not included here.  Similarly, lines constructed to any voltage may be operated at a lower voltage.

4. 400 V lines: calculations are for open-phase designs.  ABC (aerial bundled conductors) produce lower fields but are not susceptible to easy calculations.

Version 3

12 January 2005

 

back