Overhead Lines
Tables of calculated electric fields produced
by overhead lines in operation in the UK
See also the companion table for magnetic
fields, underground
fields and the simpler summary
| |
|
|
|
|
electric
field in V m-1 at distance from centreline |
|
maximum under line |
10 m |
25 m |
50 m |
100 m |
|
400 kV |
largest lines |
L6
quad bundles
0.305 m
zebra
|
maximum |
clearance 7.6 m
phasing U
|
11400 |
10130 |
774 |
446 |
156 |
|
typical |
clearance 13 m
phasing T
|
4244 |
4206 |
962 |
106 |
32 |
|
smaller lines |
L2
twin bundles
0.305 m
zebra
|
maximum |
clearance 7.6 m
phasing U
|
9897 |
6618 |
283 |
357 |
118 |
|
typical |
clearance 13 m
phasing T
|
3128 |
2964 |
469 |
56 |
27 |
|
typical design used for new lines |
L12
twin bundles
0.5 m
araucaria
|
maximum |
clearance 7.6 m
phasing U
|
10642 |
8410 |
669 |
404 |
136 |
| clearance 7.6 m
phasing T
|
9384 |
7933 |
737 |
151 |
30 |
|
typical |
clearance 13 m
phasing T
|
3704 |
3595 |
732 |
98 |
26 |
|
275 kV |
largest lines |
L6
quad bundles
0.305 m
zebra
|
maximum |
clearance 7.6 m
phasing U
|
7838 |
6964 |
532 |
307 |
107 |
|
typical |
clearance 13 m
phasing T
|
2918 |
2892 |
661 |
73 |
22 |
|
smaller lines |
L2
twin bundles
0.305 m
zebra
|
maximum |
clearance 7.6 m
phasing U
|
6804 |
4550 |
195 |
245 |
81 |
|
typical |
clearance 13 m
phasing T
|
2151 |
2038 |
322 |
39 |
19 |
|
typical design used for new lines |
L12
twin bundles
0.5 m
araucaria
|
maximum |
clearance 7.6 m
phasing U
|
7316 |
5782 |
460 |
278 |
94 |
|
typical |
clearance 13 m
phasing T
|
2547 |
2472 |
503 |
67 |
18 |
|
132 kV |
largest lines |
L7
twin bundles
0.305 m
lynx
|
maximum |
clearance 7 m
phasing U
|
3615 |
913 |
182 |
81 |
23 |
|
typical |
clearance 10 m
phasing U
|
2372 |
890 |
103 |
72 |
23 |
|
smaller lines |
L132
single conductors
0.4 sq in
|
maximum |
clearance 7 m
phasing U
|
2628 |
697 |
154 |
66 |
19 |
|
typical |
clearance 10 m
phasing U
|
1780 |
689 |
86 |
59 |
18 |
|
smallest wood-pole design |
trident
150 m span
single conductors
lynx
|
maximum |
clearance 7 m
single circuit
|
1174 |
588 |
73 |
11 |
2 |
|
typical |
clearance 10 m
single circuit
|
583 |
458 |
89 |
15 |
3 |
|
66 kV |
largest lines |
L7
twin bundles
0.305 m
lynx
|
maximum |
clearance 7 m
phasing U
|
1808 |
456 |
91 |
40 |
12 |
|
smaller lines |
L132
single conductors
0.4 sq in
|
typical |
clearance 10 m
phasing U
|
890 |
345 |
43 |
30 |
9 |
|
33 kV |
larger lines on steel pylons |
D
single conductors
r=9.8 mm
|
maximum |
clearance 5.5 m
phasing U
|
897 |
46 |
30 |
10 |
3 |
|
typical |
clearance 8 m
phasing U
|
543 |
81 |
21 |
9 |
3 |
|
smaller lines on wood poles |
wood pole
horizontal array
+-2 m
|
maximum |
clearance 5.5 m
single circuit
|
505 |
165 |
16 |
2 |
0 |
|
typical |
clearance 8 m
single circuit
|
241 |
147 |
21 |
3 |
0 |
|
11 kV |
larger lines on steel pylons |
SL11
single conductors
|
maximum |
clearance 5.5 m
phasing U
|
215 |
109 |
13 |
5 |
1 |
|
typical |
clearance 8 m
phasing U
|
122 |
82 |
8 |
4 |
1 |
|
smaller lines on wood poles |
wood pole
horizontal array
+-1.15 m
|
maximum |
clearance 5.5 m
single circuit
|
108 |
32 |
3 |
0 |
0 |
|
typical |
clearance 8 m
single circuit
|
50 |
29 |
4 |
1 |
0 |
|
400 V |
wood pole |
vertical array
50 mm2
|
maximum |
clearance 5.5 m
single circuit
|
1 |
1 |
0 |
0 |
0 |
|
typical |
clearance 8 m
single circuit
|
0 |
0 |
0 |
0 |
0 |
Notes to table:
1. Calculations performed on computer programme EM2D by John Swanson
January 2005.
2. Typical phases are T=transposed for 275 kV and 400 kV, U=untransposed
for 132 kV and below (phases apply to double-circuit lines only)
3. For electric fields, U always gives the highest maximum field
and the highest field at large distances, so is used for that reason,
but at intermediate distances from the line, electric fields are
complex, and either T or U can be higher.
4. The “maximum field under the line” is the largest field, which
is not necessarily on the route centreline; it is often under one
of the conductor bundles for a two-circuit line and can even be
outside the conductors eg for a 400 V vertical array.
5. All fields calculated at 1 m above ground level and for nominal
voltage
6. All fields are given to the same resolution for simplicity
of presentation (1 V/m) but are not accurate to better than a few
percent.
7. Calculations ignore zero-sequence voltage. This means values
at larger distances are probably underestimates, but this is unlikely
to amount to more than a few percent except for 400 V lines.
8. Generally speaking, the lower the voltage, the more different
variants of design there are. The “maximum” calculation is presented
here in good faith but may not take account of every last variant
in operation. To meet specific local circumstances, lines at 132
kV and below may occasionally have been constructed with higher
ratings. Within the legal framework of the Regulations, different
DNOs may have different policies regarding minimum clearances.
9. All calculations are for three-phase lines, single-phase lines
at low voltages have not been investigated.
Notes on specific voltages:
1. In efforts to reduce aerodynamic problems, a small number of
400 kV lines with quad bundles have had expanded bundles fitted,
eg 500 mm horizontally. This produces slightly higher electric
fields but is not included in these tables.
2. For 400 kV, L12 lines are included as these are likely to be
used for new construction. Phasing U gives the maximum field under
the line and is included for that reason but phasing T would be
used in practice so is also included.
3. 132 kV lines have, in the past, been constructed on 275/400
kV towers with a view to future uprating. This is unlikely to happen
again so is not included here. Similarly, lines constructed to
any voltage may be operated at a lower voltage.
4. 400 V lines: calculations are for open-phase designs. ABC
(aerial bundled conductors) produce lower fields but are not susceptible
to easy calculations.
Version 3
12 January 2005
back |