Transmission
Transmission lines
What is a transmission line?
A transmission line is a high-voltage overhead
power line - the lines operated by National Grid.
In England and Wales there are 7000 km of overhead
transmission lines at 275 kV and 400 kV. Virtually all of these
lines carry two separate circuits, one each side of the towers,
each with three wires or bundles of wires.
Click here for
more details on what a transmission line looks like and what its
parts are.

Examples of field lines produced by transmission lines
How do transmission lines produce fields?
The magnetic field produced by a current in a conductor
falls with distance from the conductor. Where there is more than
one current forming part of one or more electrical circuits, there
is also partial cancellation between the magnetic fields produced
by the individual currents, and that cancellation generally becomes
better at greater distances. Overall, the magnetic field is highest
at the point of closest approach to the conductors and falls quite
rapidly with distance. Similarly, there is partial cancellation
between the electric fields produced by the voltages on individual
conductors, and the electric field is usually highest at the point
of closest approach to the conductors and falls quite rapidly with
distance.
Therefore transmission lines produce a magnetic
field which peaks underneath the conductors and falls rapidly with
distance either side, as illustrated in the figure below.
More on how fields fall with distance.

What determines how much field they produce?
The actual field produced depends on several factors.
It depends on the currents. The largest lines in use have a
rating of over 4000 A per circuit, but the average current in
a typical circuit is more like 700 A.
It depends on the clearance of the line. The minimum ground
clearance of a 400 kV line is 7.6 m, but it is rare for lines
to be this low, and the ground-level field falls rapidly with
the height of the line above ground. The maximum fields that are
produced by a line occur directly underneath the line, underneath
the lowest point of the conductors, which is usually towards the
middle of each span. Actual conductor clearances above ground
would generally be higher than this (and therefore the fields
produced near ground level would be lower) for two main reasons.
Firstly, for most of the length of a span, the conductor clearance
is higher than it is at the lowest point. Secondly, the actual
ground clearance of the conductors depends on their temperature.
For the vast majority of the time they operate at less than their
rated maximum temperature and therefore sag less, resulting in
higher ground clearances.
-
The field also depends on the relative phasing
of the two circuits (see the figure below). A few lines have
"untransposed" phasing, with the phases in the same
order from top to bottom on the two sides of the towers. This
produces a field which falls as the inverse
square of distance from the line. However most lines have
"transposed" phasing, with the opposite order of the
phases on one side to the other. This introduces an extra degree
of symmetry and extra cancellation between the fields from equal
currents on the two sides; the resultant field falls more nearly
as the inverse cube of distance,
producing a much lower field at large distances from the line.
This is illustrated below.

Magnetic fields can be calculated with considerable
accuracy if the currents are known. The graph below shows the actual
field measured from a 400 kV transmission line - the red dots -
compared to the calculated field at the same instant of time.

How much field do they produce?
Taking account of all these factors, the steady-state maximum ground-level
field beneath a transmission line is 100 microteslas (µT),
but in practice fields are often below 10 µT. Similar considerations
apply to electric fields (see below). The maximum unperturbed ground-level
electric field beneath a 400 kV line is 11 kilovolt per metre (kV
m-1).

This table gives more details on fields produced
by various overhead lines:
Typical ground-level UK field
levels from overhead power lines
| |
Magnetic Field (microteslas) |
Electric Field (volts per metre) |
| The largest steel pylons (275 kV and 400 kV) |
Maximum field (under line)
Typical field (under line)
Typical field (25 m to side) |
100
5-10
1-2 |
11,000
3000-5000
200-500 |
| Smaller steel pylons (132 kV) |
Maximum field (under line)
Typical field (under line)
Typical field (25 m to side) |
40
0.5 – 2
0.05-0.2 |
4,000
1000-2000
100-200 |
Wooden poles
(11 kV and 33 kV) |
Maximum field (under line)
Typical field (under line)
Typical field (25 m to side) |
7
0.2-0.5
0.01-0.05 |
700
200
10-20 |
This is a summary. We also give a lot more detail on maximum and
typical fields from various power lines in two separate (and complex)
tables for electric
and magnetic
fields.

Examples of typical maximum fields from lines of different voltages
What is the average field from a line?
The following table gives more detail on the average magnetic field
at various distances from a typical National Grid line. These figures
were calculated from one year’s worth of recorded load data
and are the average for a representative sample of 43 different
lines.
| Distance m |
0 |
50 |
100 |
200 |
300 |
| Average Field µT |
4.005 |
0.520 |
0.136 |
0.034 |
0.015 |
How many people live near high-voltage power lines?
Although people living near high-voltage power lines are a group
whose exposure is high and can often be calculated reasonably well,
they are a small group. In the UK, 0.07% of homes are within 50
m of transmission lines and 0.21% within 100 m. Percentages in other
countries seem to be comparable (USA 1.1% within 40 m; Denmark 0.43%
within 75 m), with higher percentages partly reflecting a broader
definition of “transmission”.
More detail on numbers of homes near
power lines.
Averaged over the population, high-voltage
power lines contribute only a small fraction of collective average
exposure to EMFs, because so few people are exposed to them. The
best estimate possible from the UK is that high-voltage power lines
contribute 5% of total average population exposure.
back
|