11 kV overhead lines: magnetic field

11 kV lines are either carried on small lattice steel pylons or on wood poles.  There are many different variants of lines design but they all produce roughly similar fields.

The maximum field shown here is produced by a lattice pylon design when the ground clearance is the minimum allowed – 5.5 m – and the loads are the highest allowed – not usually above 500 A in each circuit but there may be exceptions.  The field also depends on the phasing. 11 kV lines usually have Untransposed (U) phasing.

graph showing maximum fields

Typical fields are lower than the maximum field because the clearance is usually higher and the loads are usually lower.  The two curves shown here are for typical loads, the normal U phasing, and two different line designs: a lattice steel pylon (the higher field), and a wood-pole design (the lower field).

graph showing typical field

typical 11 kV wood pole:

photo of 11 kV wood pole

This table gives some actual field values for the same conditions.

 

magnetic field in µT at distance from centreline

maximum under line

10 m

25 m

50 m

100 m

11 kV

larger lines on steel pylons

SL11

single conductors

maximum

clearance 5.5 m
phasing U
load 0.5/0.5 kA

9.456

7.664

1.490

0.364

0.090

typical

clearance 8 m
phasing U
load 0.1 kA

1.004

0.942

0.274

0.071

0.018

smaller lines on wood poles

wood pole

horizontal array

+-1.15 m

maximum

clearance 5.5 m
single circuit
load 0.2 kA

3.744

0.668

0.124

0.032

0.008

typical

clearance 8 m
single circuit
load 0.05 kA

0.399

0.134

0.030

0.008

0.002

Note:

1. All fields calculated at 1 m above ground level.

2. All fields are given to the same resolution for simplicity of presentation (1 nT = 0.001 µT) but are not accurate to better than a few percent.

3. Calculations ignore zero-sequence current.  This means values at larger distances are probably underestimates, but this is unlikely to amount to more than a few percent and less closer to the line.

4. The “maximum field under the line” is the largest field, which is not necessarily on the route centreline; it is often under one of the conductor bundles.

5. Sometimes, an 11 kV circuit could be carried on a line designed for a higher voltage.  Then the magnetic fields could be larger than shown here.

6. The dip in field on the centreline between the two circuits happens when the two circuits are carrying the same load, and is less pronounced if the loads are different.

For comparison of fields from different voltage lines click here:

link to page of comparisons

For more fields at this voltage and fields at other specific voltages see this index:

link to page of specific power lines