EMFs.info

Electric and magnetic fields and health

index/glossary | EMFs At A Glance | EMF The Facts (pdf)
  • What are EMFs
    • Terminology – an introduction
    • Electric fields
    • Magnetic fields
    • Units for measuring EMFs
    • Measuring and calculating EMFs
      • “EMF Commercial”
    • Adding fields together
    • Radiofrequencies
    • Screening EMFs
  • Sources
    • Overhead power lines
      • Fields from specific power lines
        • 400 kV
        • 400 kV – specific cases
        • 275 kV
        • 132 kV
        • 66 kV
        • 33 kV
        • 11 kV
        • 400 V/230 V
        • Replacing a 132 kV line with a 400 kV line
      • Summaries of fields from all power lines
      • Factors affecting the field from a power line
        • Voltage
        • Current
        • Clearance
        • Height above ground
        • Conductor bundle
        • Phasing
        • Balance between circuits
        • Balance within circuit
        • Ground resistivity
        • Two parallel lines
      • Calculating and measuring fields from power lines
        • Geometries of power lines
        • Raw data
        • On-line calculator
      • Fields from power lines – more detail on the physics
        • Field lines from a power line
        • The direction of the field from a power line
        • Power law variations in the field from a power line
      • Statistics of power line fields
    • Underground power cables
      • Different types of underground cable
      • Fields from cables in tunnels
      • Gas Insulated Lines (GIL)
      • Underground cables with multiple conductors
      • Effect of height on fields from underground cables
      • Screening fields from underground cables
    • Low-voltage distribution
      • UK distribution wiring
      • USA distribution wiring
    • House wiring
    • Substations
      • National Grid substations
        • Static Var Compensators
      • Sealing-end compounds
      • Distribution substations
      • Final distribution substations
        • Indoor substations
    • Transport
      • EMFs from electric trains (UK)
      • EMFs from cars
    • Appliances
    • Electricity meters
      • Smart meters
      • Traditional meters
    • Occupational exposures
      • Live-line work
      • Static Var Compensators
      • Occupational exposures on pylons
    • Field levels and exposures
      • Personal exposure
      • Other factors that vary with magnetic fields
      • Fields greater than 0.2 or 0.4 µT
    • Screening EMFs
      • Screening fields from underground cables
      • EMF Reduction Devices
  • Known effects
    • Induced currents and fields
    • Microshocks
      • Control of microshocks in the UK
      • Microshocks from bicycles
      • Bees and microshocks
    • EMFs and medical devices
      • Standards relating to pacemakers and other AIMDs
    • Effects of EMFs on equipment
  • Research
    • Types of research
    • Epidemiology
    • Animal and laboratory experiments
    • Mechanisms
    • Specific studies
      • UKCCS
      • CCRG
      • French Geocap study
      • CEGB cohort
      • Imperial College study
  • Current evidence on health
    • Childhood leukaemia
      • Survival from childhood leukaemia
      • Childhood leukaemia and Downs
      • Childhood leukaemia and night-time exposure
      • The “contact current” hypothesis
    • Other health effects
    • Scientific review bodies
      • WHO
      • IARC
    • Electric fields and ions
    • Comparing EMFs to other issues
  • Exposure limits for people
    • Limits in the UK
    • Limits in the EU
    • Limits in the USA
    • Limits in the rest of the world
    • Limits from specific organisations
      • ICNIRP 1998
      • ICNIRP 2010
      • NRPB 1993
      • NRPB 2004
      • EU 2004
      • EU 2013
  • Policy
    • UK policy
      • Power lines and property – UK
    • Compliance with exposure limits
    • European EMF policy
    • Precaution
    • SAGE
      • SAGE First Interim Assessment
        • Government response to SAGE First Interim Assessment
      • SAGE Second Interim Assessment
        • Government response to SAGE Second Interim Assessment
        • SAGE Second Interim Assessment – the full list of recommendations
  • Finding out more
    • EMF measurement and commercial services
    • Links
    • Literature
    • Contact us
  • Static fields
    • Static fields – the expert view
You are here: Home / Sources / Overhead power lines / Fields from specific power lines / 66 kV

66 kV

66 kV lines are not very common in the UK.  They are often built using one of the 132 kV line designs, so the magnetic field is the same as for 132 kV.  132 kV overhead lines are usually carried on lattice steel pylons, but smaller than used for 275 kV and 400 kV lines.  Sometimes they are carried on wood poles.

All 66 kV lines are inherently compliant with the public exposure limits - see more details

Magnetic field

The maximum field is produced by the largest design of line – the L7 – when the ground clearance is the minimum allowed – 7.0 m – and the loads are the highest allowed – 1.4 kA in each circuit.  The field also depends on the phasing. 66 kV lines usually have Untransposed (U) phasing.

graph of maximum field 66 kV 

Typical fields are lower than the maximum field because the clearance is usually higher and the loads are usually lower.  The two curves shown here are for typical loads, the normal U phasing, and two different line designs: a lattice steel pylon, L132 (the higher field), and a wood-pole design (the lower field).

graph of typical field 66 kV 

This table gives some actual field values for the same conditions.

     

magnetic field in µT at distance from centreline

maximum under line

10 m

25 m

50 m

100 m

66 kV

largest lines

L7
twin bundles
0.305 m
lynx

maximum

clearance 7 m
phasing U
load 1.4/1.4 kA

30.445

20.532

5.553

1.528

0.392

typical

clearance 10 m
phasing U
load 0.13/0.13

1.848

1.359

0.468

0.138

0.036

smaller lines

L132
single conductors
0.4 sq in

maximum

clearance 7 m
phasing U
load 1.2/1.2 kA

24.585

17.217

4.587

1.247

0.318

typical

clearance 10 m
phasing U
load 0.13/0.13 kA

1.731

1.317

0.451

0.132

0.034

smallest wood-pole design

trident
150 m span
single conductors
lynx

maximum

clearance 7 m
single circuit
load 0.7 kA

12.347

12.347

0.738

0.192

0.048

typical

clearance 10 m
single circuit
load 0.1 kA

1.764

0.385

0.099

0.027

0.007

Note:

1. All fields calculated at 1 m above ground level.

2. All fields are given to the same resolution for simplicity of presentation (1 nT = 0.001 µT) but are not accurate to better than a few percent.

3. Calculations ignore zero-sequence current.  This means values at larger distances are probably underestimates, but this is unlikely to amount to more than a few percent and less closer to the line.

4. The “maximum field under the line” is the largest field, which is not necessarily on the route centreline; it is often under one of the conductor bundles.

5. Sometimes, a 66 kV circuit could be carried on a line designed for 275 kV or 400 kV.  Then the magnetic fields could be larger than shown here.  Or it could be carried on a one-off wood pole design, but the fields would probably be similar to those shown here.

Electric field

The maximum field is produced by the largest design of line – the L7 – when the ground clearance is the minimum allowed – 7.0 m. The field also depends on the phasing. 66 kV lines usually have Untransposed (U) phasing.

graph of maximum field 66 kV 

Typical fields are lower than the maximum field because the clearance is usually higher. The curve shown here is for the normal U phasing, and a typical medium-size lattice steel pylon.

graph of typical field 66 kV 

This table gives some actual field values for the same conditions.

     

electric field in V m-1 at distance from centreline

maximum under line

10 m

25 m

50 m

100 m

66 kV

largest lines

L7
twin bundles
0.305 m
lynx

maximum

clearance 7 m
phasing U

1808

456

91

40

12

smaller lines

L132
single conductors
0.4 sq in

typical

clearance 10 m
phasing U

890

345

43

30

9

Note:

1. All fields calculated at 1 m above ground level.

2. All electric fields are calculated for the nominal voltage.  In practice, voltages (and hence fields) may rise by a few percent.

3. All electric fields calculated here are unperturbed values.

4. All fields are given to the same resolution for simplicity of presentation (1 V/m) but are not accurate to better than a few percent.

5. Calculations ignore zero-sequence voltages.  This means values at larger distances are probably underestimates, but this is unlikely to amount to more than a few percent and less closer to the line.

6. The “maximum field under the line” is the largest field, which is not necessarily on the route centreline; it is often under one of the conductor bundles.

7. Sometimes, a 66 kV circuit could be carried on a line designed for 275 kV or 400 kV.  Then the electric fields could be larger than shown here.  Or it could be carried on a one-off wood pole design, but the fields would probably be similar to those shown here.

Underground cables

66 kV is not a common voltage, and 66 kV underground cables are even rarer.  Where they exist, they would be similar to 132 kV underground cables

Other voltages:

  • 400 kV
  • 400kV special cases
  • 275 kV
  • 132 kV
  • 66 kV
  • 33 kV
  • 11 kV
  • 400 V/230 V

Latest news

  • New publication on cancer incidence from the UK electricity industry Cohort Study August 27, 2019
  • How has the reported risk for childhood leukaemia changed over time? February 11, 2019
  • Media stories about microshocks in children’s playground September 10, 2018
  • New studies on leukaemia and distance from power lines June 1, 2018
older news

Contact Us

To contact the electricity industry’s EMF Unit Public Information Line (UK only):
telephone 0845 7023270 or email [email protected].

See Contact us for more contact details including our privacy policy.

About this site

  • What this site covers and what it doesn’t
  • Industry policy
  • Sitemap

Specific questions

  • Affected by a new power line or substation?
  • Building or developing near a power line or substation?
  • EMF measurement and commercial services
  • Microshocks
  • Pacemakers and other medical devices
  • EMF policy in the UK
Site Authorship |Sitemap | Terms and Conditions | Privacy Policy | Cookies | Site Statistics
© 2021 EMFS.info
Navigation
  • What are EMFs
    • Terminology – an introduction
    • Electric fields
    • Magnetic fields
    • Units for measuring EMFs
    • Measuring and calculating EMFs
      • “EMF Commercial”
    • Adding fields together
    • Radiofrequencies
    • Screening EMFs
  • Sources
    • Overhead power lines
      • Fields from specific power lines
        • 400 kV
        • 400 kV – specific cases
        • 275 kV
        • 132 kV
        • 66 kV
        • 33 kV
        • 11 kV
        • 400 V/230 V
        • Replacing a 132 kV line with a 400 kV line
      • Summaries of fields from all power lines
      • Factors affecting the field from a power line
        • Voltage
        • Current
        • Clearance
        • Height above ground
        • Conductor bundle
        • Phasing
        • Balance between circuits
        • Balance within circuit
        • Ground resistivity
        • Two parallel lines
      • Calculating and measuring fields from power lines
        • Geometries of power lines
        • Raw data
        • On-line calculator
      • Fields from power lines – more detail on the physics
        • Field lines from a power line
        • The direction of the field from a power line
        • Power law variations in the field from a power line
      • Statistics of power line fields
    • Underground power cables
      • Different types of underground cable
      • Fields from cables in tunnels
      • Gas Insulated Lines (GIL)
      • Underground cables with multiple conductors
      • Effect of height on fields from underground cables
      • Screening fields from underground cables
    • Low-voltage distribution
      • UK distribution wiring
      • USA distribution wiring
    • House wiring
    • Substations
      • National Grid substations
        • Static Var Compensators
      • Sealing-end compounds
      • Distribution substations
      • Final distribution substations
        • Indoor substations
    • Transport
      • EMFs from electric trains (UK)
      • EMFs from cars
    • Appliances
    • Electricity meters
      • Smart meters
      • Traditional meters
    • Occupational exposures
      • Live-line work
      • Static Var Compensators
      • Occupational exposures on pylons
    • Field levels and exposures
      • Personal exposure
      • Other factors that vary with magnetic fields
      • Fields greater than 0.2 or 0.4 µT
    • Screening EMFs
      • Screening fields from underground cables
      • EMF Reduction Devices
  • Known effects
    • Induced currents and fields
    • Microshocks
      • Control of microshocks in the UK
      • Microshocks from bicycles
      • Bees and microshocks
    • EMFs and medical devices
      • Standards relating to pacemakers and other AIMDs
    • Effects of EMFs on equipment
  • Research
    • Types of research
    • Epidemiology
    • Animal and laboratory experiments
    • Mechanisms
    • Specific studies
      • UKCCS
      • CCRG
      • French Geocap study
      • CEGB cohort
      • Imperial College study
  • Current evidence on health
    • Childhood leukaemia
      • Survival from childhood leukaemia
      • Childhood leukaemia and Downs
      • Childhood leukaemia and night-time exposure
      • The “contact current” hypothesis
    • Other health effects
    • Scientific review bodies
      • WHO
      • IARC
    • Electric fields and ions
    • Comparing EMFs to other issues
  • Exposure limits for people
    • Limits in the UK
    • Limits in the EU
    • Limits in the USA
    • Limits in the rest of the world
    • Limits from specific organisations
      • ICNIRP 1998
      • ICNIRP 2010
      • NRPB 1993
      • NRPB 2004
      • EU 2004
      • EU 2013
  • Policy
    • UK policy
      • Power lines and property – UK
    • Compliance with exposure limits
    • European EMF policy
    • Precaution
    • SAGE
      • SAGE First Interim Assessment
        • Government response to SAGE First Interim Assessment
      • SAGE Second Interim Assessment
        • Government response to SAGE Second Interim Assessment
        • SAGE Second Interim Assessment – the full list of recommendations
  • Finding out more
    • EMF measurement and commercial services
    • Links
    • Literature
    • Contact us
  • Static fields
    • Static fields – the expert view