A National Grid substation is a large installation where 275 kV and 400 kV overhead power lines or underground cables are switched and where electricity is transformed to 132 kV for distribution to surrounding areas. Each substation can be a hundred metres or more across and is surrounded by a metal fence (a few are indoors in suitably large buildings).
Normally, the field from the equipment inside a substation does not extend much if at all beyond the perimeter fence - the field outside the perimeter comes from the overhead lines or underground cables entering or leaving the substation.
Electric fields - simple version
The metal fence surrounding the substation ensures that almost no electric fields emerge from the substation itself. Any electric fields round the substation will come almost entirely from the overhead power lines entering it.
Electric fields - more detail
Large National Grid substations do not produce significant electric fields outside their boundary because the perimeter fence screens the electric field from any sources within the substation.
Inside the substation, the various busbars and other equipment do produce electric fields. These are highest where the arrangement of busbars means that the fields from adjacent busbars reinforce each other, and lower where the arrangement produces cancellation.
This diagram was produced in the 1980s after extensive measurements in a 400 kV substation chosen because the arrangement of busbars was likely to produce the highest field possible.
It is not very clear to see (click on the diagram for a hi-res version if you want to see all the numbers), but in most regions, the field is between 5 and 10 kV/m. But in small regions where the busbars reinforce each other, the field rose to 21 kV/m:
Note that these readings were taken at head height, 1.8 m above ground. The standard now for assessing fields is 1 m above ground, where the fields would be slightly lower.
Magnetic fields - simple version
There is equipment inside substations which produces magnetic fields. But the field falls with distance quite rapidly, and by the time you are at the perimeter fence or a few metres outside it, the magnetic field from inside the substation is usually approaching background levels. Again, the largest magnetic fields round the perimeter of a substation almost always come from the overhead lines and underground cables entering it. There are often several such lines and it can be difficult distinguishing the field from the substation itself from the fields produced by these lines.
Sometimes, if a transformer is located inside the substation close to the perimeter fence, the magnetic field produced by the cables or busbars supplying the transformer can cause an elevated magnetic field outside the fence. The same thing can happen if something called a reactor or a static var compensator is very close to the perimeter. But generally, away from any overhead lines entering the substation, the magnetic field at the perimeter fence would be perhaps a microtesla.
Magnetic fields - more detail
Substations become very complicated, with many different sections of conductor carrying currents in different directions, and calculating the fields from them gets very complex. We illustrate the fields produced by an unusually simple example (actually Birkenhead Substation). One double-circuit enters the substation, and through a simple arrangement of busbars and switchgear is connected to three transformers (only two operating under the conditions of this modelling). The current leaves the substation through busbars (to an adjoining 132 kV substation, though this is not included in our model).
The following contour plot shows the magnetic fields produced by this simple arrangement, for a typical load flowing into the substation of 1300 A:
This confirms that the highest fields at the closest public approach (the perimeter fence) are where the overhead line enters the substation. The fields under the busbars crossing the perimeter fence are slightly higher, because these busbars are at a lower clearance than the overhead line, but this is not a publicly accessible area. All these fields are well below the public exposure limits.
See also:
- fields from other types of substation
- static var compensators - one item of equipment in some substations
- Sealing End Compounds - similar to a small substation